Air principle · displacement
The air comes in low and lets the heat do the work.
In displacement ventilation, cool air leaves a large outlet so slowly that it does not mix. It spreads as a thin layer across the floor and creeps through the room. At every heat source, a person, a machine, it rises and carries heat and contaminants up to the ceiling, where it is extracted.
What the air does
Low, slow, creeping.
At the outlet
Discharge velocity usually 0.2 m/s at most, with little turbulence, from an outlet with a large face. (DS 4069 E p. 2)
Across the floor
Beyond the zone near the outlet, the air flows in a very thin layer, usually less than 200 mm. Most of it glides on to the opposite wall. (DS 4069 E p. 8)
At the heat source
People, lighting and equipment lift the air. Without internal heat sources, displacement does not work. (DS 4069 E p. 2)
With height
The temperature rises gradually towards the ceiling. The lower zone stays virtually clean: that is where you draw your breathing air. (DS 4069 E p. 2–3)
Character
Low turbulence: a turbulence intensity of 25 % at most (DS 4069 E p. 3); TB 69 uses 20 % (p. 3).
When to choose displacement
Many people, clean air.
- Auditoria, theatres, lecture halls. Many heat sources close together, and the air enters right next to the audience: from the steps, the seat pedestal or the floor.
- Museums and foyers. Calm air, little air movement, outlets along walls or columns.
- Industrial halls. Contaminants rise with the heat and are extracted above the working zone. For halls without chillers there are hybrid types that add air movement in hot weather (VA-ZH, VA-LH).
When not: With a high cooling load per m², or if heating is the main task. Heating is only possible with displacement outlets designed for it (DS 4069 E p. 2). Otherwise, look at mixing →.
Design limits: comfort
The rules from DS 4069 and TB 69.
category A to EN ISO 7730
(DS 4069 E p. 4)
- Supply air at most 3 K below room air
- Air just above the floor at least 21 °C
- Difference room – floor at most 2 K
gradient and cooling load
(TB 69 p. 4)
- Temperature difference between 0.1 and 1.1 m: A < 2 K · B < 3 K · C < 4 K
- Rule of thumb for displacement: at most 45 W/m² (A) and 55 W/m² (B)
air velocity in the occupied zone at 26 °C
(TB 69 table 2)
- A 0.18 · B 0.32 · C 0.45 m/s
air volume
(DS 4069 E p. 4)
- In offices usually at most 20 m³/(h·m²)
The near zone
Close to the outlet, the air can move faster than is comfortable. At about half a metre to one and a half metres it reaches its highest velocity, then slows again (DS 4069 E p. 2). That zone should stay free of fixed workstations. Krantz specifies it as the distance at which the velocity has dropped to 0.2 m/s (p. 4).
| Position | Near zone (indicative) | Source |
|---|---|---|
| Floor outlet | approx. 1 m | DS 4069 E p. 7 |
| Outlet at ceiling level or in the corridor wall (≤ 0.25 m/s) | approx. 2 m | DS 4069 E p. 7 |
| Rectangular outlet > 500 mm high, as a continuous band | keep the first 2 m unoccupied | DS 4069 E p. 6 |
Penetration depth
In the standard case the cool layer reaches the far side of the room (DS 4069 E p. 8).
The supply air must not be warmer than the room, or it will not penetrate far enough (DS 4069 E p. 8).
Step displacement
Air from the step.
In a hall with raked seating, the air comes from the riser of the step, directly behind the seats. It is fed from a pressure plenum below the steps and leaves through a finely perforated face plate. A flow straightener lifts the flow just off the floor. The cool layer rises around the audience to the breathing zone. (DS 4054 E p. 2, p. 4, p. 8)
Q-SL
(DS 4054 E)
- Discharge velocity · 0.18 m/s · p. 5
- At the feet up to 0.17 m/s; above 0.3 m < 0.10 m/s · p. 4
- ΔT supply – room up to −4 K; supply – exhaust up to −12 K; supply 19 °C · p. 5
- Temperature gradient up to 2 K/m · p. 4
Q-SR
· DN 80 max. 36 m³/h for one person; DN 100 max. 59 m³/h for two (DS 4054 E p. 4)
Types: Q-SL (linear, continuous band) · Q-SR (round, per seat) · Q-ST (in the seat pedestal) · SD-L (linear step swirl outlet)
Design limits: industry
Halls, from 3 to 30 m.
Factories follow different air velocities, to VDI 3802, depending on activity and clothing. At 26 °C, moderate standing work (2 met) and standard work clothing (0.9 clo), up to 0.41 m/s is allowable; at 28 °C up to 0.45 m/s. Because activity varies per workstation, Krantz recommends adjustable displacement outlets. (TB 69 p. 7)
| Type | Position | Height | Max. ΔT | Key point | Source |
|---|---|---|---|---|---|
| VA-PV | high above the occupied zone | 4–8 m | −6 K cooling; heating +10 K (p. 8) | vertically down, support jet for heating | DS 4061 E p. 2 |
| VA-K | ceiling, very high halls | 6–30 m | −5 K / +8 K | coverage radius approx. 3–5 m | DS 4011 E p. 3–4 |
| VA-ZD | approx. 3 m or on the floor | — | ±10 K above the occupied zone | supply depth up to approx. 20 m | DS 4059 E p. 11 |
| VA-ZH | approx. 3 m above the floor | — | — | switchable jet nozzles | DS 4203 E p. 2–3 |
| VA-LH | wall or column | 3–5 m | — | linear, hybrid | DS 4202 E p. 2–3 |
| VA-RV · VA-RN | floor, along the wall | — | −8 K / +6 K (VA-RV) | cooling reach up to 20 m | DS 4009 E p. 2, p. 5 |
| VA-S | on the supply duct | 3–5 m | ±8 K | swivelling front | DS 1276 E p. 3 |
| VA-T · VA-TH | below the duct, or in front of wall or column | 3–4 m | −3 to −8 K (VA-T) | permanent cooling | DS 4010 E p. 7 |
Typical mistakes
Where it goes wrong.
- A fixed workstation in the near zone. The air is faster than comfortable there. Keep the zone clear, or choose an outlet with a smaller near zone.
- Supply too cold. More than 3 K below room temperature in category A means cold feet and too steep a gradient (DS 4069 E p. 4).
- Too much cooling load. Above 45 W/m² (A) or 55 W/m² (B) the gradient between feet and head increases (TB 69 p. 4). Combine with a chilled ceiling, or choose mixing.
- Warm supply air. Warmer than the room, the air does not penetrate far enough (DS 4069 E p. 8). Heat with a type made for it, such as the VA-PV or VA-K with support jet.
- A room without heat sources. Nothing rises, so the principle does not work (DS 4069 E p. 2).
- The displacement pattern disturbed by mixing. An additional outlet blowing with high momentum breaks up the cool layer.
The types in the collection
Comfort, floor and wall: Q-R · Q-Z · Q-ZH · Q-W · Q-S (skirting)
Comfort, floor outlets: Q-B · Q-B-DN 215 · Q-BR · BA-V (switches between swirl and displacement)
Comfort, ceiling: Q-DN · Q-DV
Step and seat: Q-SL · Q-SR · Q-ST · SD-L
Industry: VA-PV · VA-K · VA-ZD · VA-ZD-L · VA-ZH · VA-LH · VA-RV · VA-RN · VA-S · VA-T · VA-TH
Façade: IG-Q-SB (induction unit for displacement)
Where you’ll find it
Krantz displacement outlets in Dutch projects, according to the old Peek website: Rijksmuseum, Amsterdam (VA-PV and Q-R); Amphion Theater, Doetinchem (Q-SL); TivoliVredenburg, Utrecht (Q-SR); Heineken, ‘s-Hertogenbosch (VA-PV); Lakhal 14, Schiphol (VA-K).
Your host
Tell Pia about your space.
Pia is Peek's digital host. Describe your hall or building, and she will show you the Krantz components that fit.
I'm Pia. Shall I show you around?
Pia is an AI avatar, not a person.
with sound and microphone
Not live. Pia only starts when you click.
Click the start button in Pia's window. Your browser will then ask for your microphone.
Prefer a call? Leave your name and number and we'll call you back. Or chat with Pia using the button at the bottom right.
Or call us: +31 (0)73 820 02 88