Krantz Components

The ConeDisplacement · supporting jet for heatingseen from below

VA-K

Conical displacement outlet for very high halls

VA-K Conical displacement outlet for very high halls by Krantz

blue = cool supply air orange = warm air

Move through the air · click for a gentle displacement flowDrag the diffuser to rotate · tap beside it for a gentle displacement flow

For extremely high halls. A cone-shaped outlet brings the air down with low turbulence, from 6 to 30 m. (DS 4011 E p. 2–4)

VA-K Conical displacement outlet for very high halls by Krantz
VA-KDisplacement · displacement
Max. ΔT cooling
max. −5 K (toevoer-afvoer)p. 3
Source · DS 4011 EKrantz, Conical displacement outlet VA-K, DS 4011 E 07.2014/1

Stylised view, not a measurement

Air principle

From outlet to occupied zone.

At the outlet

A perforated cylinder with a conical neck lets the air out with low turbulence. (DS 4011 E p. 3)

In the room

For cooling the air sinks gently to the floor; one outlet covers a radius of approx. 3 – 5 m. For heating an actuator opens the core tube and the annular gap, and a supporting jet pushes the warm air down. (DS 4011 E p. 2–4)

Construction

A circular housing with spigot, the perforated cylinder with conical neck, a core tube with rounded inlet, and damper discs coupled to the annular seal. An electric actuator drives the assembly. (DS 4011 E p. 2)

Smoke test

Airflow in the Krantz lab.

A real smoke test in the Krantz flow laboratory: this is how air leaves the VA-K.

VA-KVideo: Krantz Komponenten · Real smoke test in the laboratory

Technical data VA-K

Discharge height
6 – 30 mp. 6
Max. ΔT cooling
−5 Kp. 3
Volume flow
1 000 – 10 000 m³/hp. 7

Krantz Components, Conical displacement outlet VA-K, DS 4011 E 07.2014/1.

Page numbers are PDF pages of the data sheet.

Download documents

Request CAD/BIM

We will send you the available CAD or BIM files for the VA-K, or call you to hear exactly what you need.

We use your details only to handle this request and do not store them on the website. More in our privacy statement.

Air

Specifications of the VA-K with the source of each value · Air
PropertyValue · Source
Air distribution displacement, low turbulence; supporting jets via core tube and annular gap for heating DS 4011 E p. 3
Volume flow 1 000 – 10 000 m³/h p. 7
Nominal volume flow DN 630: 2 500 m³/h · DN 800: 10 000 m³/h p. 7
Max. ΔT cooling −5 K (supply – extract) p. 3
Max. ΔT heating +8 K; short warm-up up to +10 K p. 3
Discharge height 6 – 30 m; DN 630 approx. 6 – 18 m, DN 800 approx. 8 – 28 m p. 6 (p. 2: up to 30 m)
Coverage coverage radius approx. 3 – 5 m per outlet; centre spacing approx. 5 – 9 m p. 4
Sound and pressure drop in charts per size, for cooling, heating and isothermal mode p. 7

Design

Specifications of the VA-K with the source of each value · Design
PropertyValue · Source
Sizes DN 630 · DN 800; outer diameter 1 060 / 1 625 mm; height 720 / 1 250 mm; approx. 96 / 220 kg table 1, p. 2
Material galvanised sheet steel; visible parts RAL 9010 or other RAL p. 7
Connection spigot; circular flange on request p. 2
Actuator built-in, electric, 0 – 10 V; damper disc stroke 0 – 100 mm (DN 630) or 0 – 120 mm (DN 800) p. 7

Versions and sizes

Two sizes, for 6 to 30 m.

  • DN 630
  • DN 800

DS 4011 E p. 2

Finish

visible parts RAL 9010 pure white or another RAL colour (p. 7)

Installation

flush with the ceiling or free-hanging, in very high halls (DS 4011 E p. 2)

Applications

Where it belongs.

Aircraft paint booths and hangars (26 m high) and sports halls such as ice rinks, there combined with the swivel jet outlet SW (DS 1249 E) (DS 4011 E p. 2). The data sheet lists as Krantz references the paint hangars of Aircraft Services Lemwerder and Deutsche Airbus Hamburg (p. 9).

When not: Below 6 m discharge height the VA-PV fits (4 – 8 m, DS 4061 E p. 2) or the VA-ZD (approx. 3 m or at floor level, DS 4059 E p. 3).

Related in the collection

Same family, a different character.

TypeWhat it isEssenceSource
VA-PVRadial displacement outletvertically down from 4 – 8 m; supporting jet for heatingDS 4061 E p. 2–3
VA-ZDCircular displacement outlet with adjustable damperapprox. 3 m above the floor or at floor level; supply depth approx. 20 mDS 4059 E p. 3, p. 11
DD-VGTwist outlet with jet straightenermixing instead of displacement; 3 – 28 mDS 4033 E p. 2

Video call with Pia

Tell Pia about your space.

Pia is Peek's digital host. Describe your hall or building, and she will show you the Krantz components that fit.

I'm Pia. Shall I show you around?

Pia is an AI avatar, not a person.

with sound and microphone

Your voice and the conversation go via Runway in the United States, where privacy protection is weaker than in the EU; we do not yet have a data processing agreement with them. By clicking the start button you give your explicit consent to this (see the privacy statement).

Not live. Pia only starts when you click.

Prefer a call? Leave your name and number and we'll call you back. Or chat with Pia using the button at the bottom right.

Or call us: +31 (0)73 820 02 88

Video call with Pia

What do you think of the new site?

Your answer helps us improve the site.

Your rating

1 = needs a lot of work, 5 = very good

We receive your rating, your text, the page you were on and, only if you fill it in, your email address, by email at Peek. More in the privacy statement.