How the VA-ZD works.
A perforated cylinder whose internal damper sets the direction steplessly, from slightly upward for cooling to straight down for heating.
Applications: production and work areas; foundries, press shops, machining (p. 4–5). The data sheet shows Tijl, Zwolle (p. 4).
Krantz, Circular displacement outlet with adjustable damper VA-ZD, DS 4059 E 04.2018.
Smoke test
Airflow in the Krantz lab.
A real smoke test in the Krantz flow laboratory: this is how air leaves the VA-ZD.
Technical data VA-ZD
- Discharge height
- aanbevolen ca. 3 mp. 3
- Max. ΔT cooling
- above the occupied zone max. ±10 Kp. 11
- Volume flow
- 194/700 – 10,000 m³/h when installedp. 2
Krantz, Circular displacement outlet with adjustable damper VA-ZD, DS 4059 E 04.2018.
Page numbers are PDF pages of the data sheet.
Download documents
Air
| Property | Value · Source |
|---|---|
| Volume flow | 194/700 – 10,000 m³/h when installed at 3 m; on the floor 500 – 7,000 m³/h p. 2 |
| Max. ΔT cooling | above the occupied zone max. ±10 K; on the floor min. supply temperature 18 °C p. 11 |
| Max. ΔT heating | above the occupied zone max. ±10 K; on the floor max. +10 K p. 11 |
| Discharge height | aanbevolen ca. 3 m (onderkant rooster) of op de vloer / sokkel max. 0.5 m p. 3 |
| Penetration depth / throw | primary penetration depth up to approx. 14 m, maximum supply depth approx. 20 m; on the floor L1max approx. 10 m (DN 250) to 25 m (DN 630), −30 % at > 120 W/m² p. 11 |
| Example sound and pressure drop | example 3 m, DN 450, 4,500 m³/h: 63 dB(A), 110 Pa; floor DN 450, 3,510 m³/h: 62 dB(A), 90 Pa p. 6 |
| Contaminant load factor | at 3 m: 55 – 57 % (mixing ventilation 90 – 100 %); on the floor approx. 20 %; heat load factor approx. 65 % and 45 % respectively p. 2 |
Design
| Property | Value · Source |
|---|---|
| Sizes | DN 250/315/355/450/560/630; Ø DA 249 – 629 mm; L 900/1,100 mm; weight 10 – 21 kg p. 2 |
| Materials and finish | galvanised sheet steel; visible parts optionally RAL (9006 semi-matt); stainless steel on request p. 12 |
| Connections | for ducts to EN 1506 p. 11 |
| Options and versions | adjustment via Bowden cable, chain pull, lever, Belimo actuator 0 – 10 V (LM24A-SR) or thermal controller TS (supply temp.) / TD (temperature difference); volume flow damper; wall or L-bracket fixing p. 12 |
Your host
Tell Pia about your space.
Pia is Peek's digital host. Describe your hall or building, and she will show you the Krantz components that fit.
I'm Pia. Shall I show you around?
Pia is an AI avatar, not a person.
with sound and microphone
Your voice and the conversation go via Runway in the United States, where privacy protection is weaker than in the EU; we do not yet have a data processing agreement with them. By clicking the start button you give your explicit consent to this (see the privacy statement).
Not live. Pia only starts when you click.
Click the start button in Pia's window. Your browser will then ask for your microphone.
Prefer a call? Leave your name and number and we'll call you back. Or chat with Pia using the button at the bottom right.
Or call us: +31 (0)73 820 02 88