Air principle
From outlet to occupied zone.
At the outlet
A finely perforated circular face plate in the step riser. (DS 4054 E p. 4)
In the room
The air spreads radially and low across the floor. Air velocities drop sharply as a result. (DS 4054 E p. 4)
Construction
A circular housing with fixed throttle and a discharge flange carrying the perforated face plate, sealing strip and claw or screw fixing. (DS 4054 E p. 3)
Technical data Q-SR
- Max. ΔT heating
- not stated
- Volume flow
- DN 80: max. 35 m³/hp. 4
Krantz Components, Step displacement outlets Q-S (Q-SR, Q-SL), DS 4054 E 07.2019.
Page numbers are PDF pages of the data sheet.
Download documents
Air
| Property | Value · Source |
|---|---|
| Air distribution | displacement, radial, low turbulence DS 4054 E p. 4 |
| Volume flow | DN 80: max. 35 m³/h, for 1 person · DN 100: max. 60 m³/h, up to 2 persons p. 4 |
| ΔT supply – room | down to −4 K p. 5 |
| ΔT supply – extract | down to −12 K p. 5 |
| Supply temperature | 19 °C p. 5 |
| Sound and pressure drop | DN 80, 25 – 36 m³/h: 19 – 36 Pa, 14 – 24 dB(A) · DN 100, 40 – 59 m³/h: 18 – 42 Pa, 14 – 27 dB(A) p. 5 |
| Max. ΔT heating | not stated |
Design
| Property | Value · Source |
|---|---|
| Sizes | DN 80 and DN 100; depth 80 mm p. 3 |
| Visible diameter | DN 80: 146 mm · DN 100: 212 mm (the dimension table gives ø DA1 195 mm for DN 100) p. 5, p. 3 |
| Min. spacing | 500 mm (DN 80) · 1 100 mm (DN 100) p. 3 |
| Material | galvanised sheet steel, visible part in RAL p. 8 |
| Fixing | 2 claws (K) or drywall screws (S, DN 100 only), for gypsum, calcium sulphate or fibre cement board p. 8 |
| Connection | air from a pressure plenum; fixed throttle in the circular housing p. 3 |
Versions and sizes
Two sizes, one per seat or per two.
- DN 80
- DN 100
DS 4054 E p. 3
Finish
visible part in RAL (p. 8)
In the auditorium
in a circular cut-out or bore in the step riser; timber or concrete steps (p. 2–3)
Applications
Where it belongs.
Lecture halls, conference halls and theatres, with timber or concrete steps (DS 4054 E p. 2).
Krantz references in the Netherlands: TivoliVredenburg, Utrecht (Q-SR); Schouwburg Kampanje, Den Helder (Q-SR); the Q-SR/Q-SL product page also lists De Doelen, Rotterdam and Tuschinski, Amsterdam
When not: For a continuous band behind the seats the Q-SL fits better (up to 75 m³/(h·m), DS 4054 E p. 5).
Related in the collection
Same family, a different character.
| Type | What it is | Essence | Source |
|---|---|---|---|
| Q-SL | Linear step displacement outlet | strip in the step riser; up to 75 m³/(h·m) at 0.18 m/s | DS 4054 E p. 5 |
| Q-ST | Seat displacement outlet | DN 100 · 127 · 190; ≤ 16 dB(A) | DS 4028 E p. 2, p. 4 |
| DS-RA-DN 80 | Circular step twist outlet | mixes quickly around the seated visitor; max. 25 m³/h | DS 4177 E p. 2 |
Video call with Pia
Tell Pia about your space.
Pia is Peek's digital host. Describe your hall or building, and she will show you the Krantz components that fit.
I'm Pia. Shall I show you around?
Pia is an AI avatar, not a person.
with sound and microphone
Your voice and the conversation go via Runway in the United States, where privacy protection is weaker than in the EU; we do not yet have a data processing agreement with them. By clicking the start button you give your explicit consent to this (see the privacy statement).
Not live. Pia only starts when you click.
Click the start button in Pia's window. Your browser will then ask for your microphone.
Prefer a call? Leave your name and number and we'll call you back. Or chat with Pia using the button at the bottom right.
Or call us: +31 (0)73 820 02 88