How the Q-BR works.
A long floor unit along the façade. The air first mixes upward with the warm façade air and then flows into the room as a cool layer across the floor.
Applications: commercial rooms with raised floor or floor plenum, along the façade (p. 2).
Krantz, Rectangular floor displacement outlet Q-BR, DS 4169 E 12.2010.
Technical data Q-BR
- Max. ΔT cooling
- supply – room −1 to −6 Kp. 2
- Volume flow
- up to 200 m³/(h·m)p. 2
Krantz, Rectangular floor displacement outlet Q-BR, DS 4169 E 12.2010.
Page numbers are PDF pages of the data sheet.
Download documents
Air
| Property | Value · Source |
|---|---|
| Volume flow | up to 200 m³/(h·m) p. 2 |
| Max. ΔT cooling | supply – room −1 to −6 K p. 2 |
| Penetration depth / throw | reach up to 6 m from the outlet p. 2 |
| Example sound and pressure drop | 2× DN 100, 100 m³/(h·m): 21 dB(A), 7 Pa; 2× DN 125, 200 m³/(h·m) [200]: 33 dB(A), 14 Pa p. 3 |
Design
| Property | Value · Source |
|---|---|
| Sizes | length 800–1,900 mm (standard 1,200); depth 140/180/260/340 mm (standard 260); height 190 mm (130 mm with bottom connection) p. 4 |
| Materials and finish | housing galvanised steel RAL 7024; grille and support frame natural anodised aluminium p. 4 |
| Connections | 2× DN 100 or 2× DN 125, front or bottom p. 4 |
| Load capacity | puntlast 1.5 kN op 200×200 mm; gelijkmatig 3.0 kN/m² p. 2 |
| Options and versions | louvred grille, cross grille or roll-up grille; single- or two-sided discharge p. 4 |
Your host
Tell Pia about your space.
Pia is Peek's digital host. Describe your hall or building, and she will show you the Krantz components that fit.
I'm Pia. Shall I show you around?
Pia is an AI avatar, not a person.
with sound and microphone
Not live. Pia only starts when you click.
Click the start button in Pia's window. Your browser will then ask for your microphone.
Prefer a call? Leave your name and number and we'll call you back. Or chat with Pia using the button at the bottom right.
Or call us: +31 (0)73 820 02 88