Air principle · induction
A thin jet takes the room along.
Air leaving a narrow opening at speed draws in the air around it. That is induction. An induction diffuser uses dozens of small jets at once; a chilled beam uses it to pull room air through a heat exchanger. A little supply air sets a lot of room air in motion.
What the air does
Many jets, one mixture.
Induction diffuser
A row of rotatable elements, each with two jet channels, forms many single jets with high induction. You set the direction per element: two-way, one-way or closed. (IN-V, DS 4082e p. 2–3, p. 14) In the IN-N6 the channels are fixed at 45°, alternately left and right. (DS 1125 E p. 2)
Wall outlet
In the BF-V, rotatable nozzle discs produce thin jets that carry along the gentle air from the perforated face plate. The result is a wide, stable fan of air. (DS 4101 E p. 2)
Active chilled beam
Primary air from nozzles pulls room air through the heat exchanger. The mixture is cooled or heated and flows horizontally along the ceiling into the room. (DK-LIG/Z, DS 4108 E)
Chilled sail with induction unit
In AVACS, the induction unit discharges about 70 % of the air above the panel and 30 % below it. (DS 4170 E p. 2)
When to choose induction
Discreet, yet powerful.
- A slim line in the ceiling. The IN-V3 is 15 mm wide per row and disappears into the ceiling (DS 4082e p. 2, p. 13).
- Direction per zone. Because every element is set individually, one linear diffuser can serve façade, corridor and workstation.
- Water carries the load. In a chilled beam or façade unit, water removes most of the cooling load. The primary air is then mainly for ventilation and induction.
- Highly glazed façades. Induction units in the floor or the parapet discharge in front of the glass (IG-M-LB DS 4137 E p. 2; IG-M-SB DS 4139 E p. 2).
When not: Above 7 m, even the IN-N6 is out of range. Look at adjustable swirl diffusers →.
Design limits
The limits per type.
| Type | Kind | Discharge height | Max. ΔT cooling / heating | Air volume | Source |
|---|---|---|---|---|---|
| IN-V (IN-V2) | linear induction diffuser, adjustable | 2.7–5 m | −10 K / +6 K | 40–400 m³/(h·m) | DS 4082e p. 2, p. 13 |
| IN-V (IN-V3) | same, 15 mm | 2.5–3.5 m | −10 K / +6 K | 11–61 m³/(h·m) | DS 4082e p. 2, p. 13 |
| IN-N6 | linear induction diffuser, fixed direction | 4–7 m | −10 K / +6 K | 100–300 m³/(h·m) | DS 1125 E p. 2, p. 6 |
| BF-V | broad wall outlet | mounting 2.2–4.0 m | −10 K / +10 K | 79–540 m³/h | DS 4101 E p. 3–4, p. 7 |
| DK-LIG/Z | active chilled beam, two-way | — | air −8 K at the stated capacities | 15–90 m³/(h·m) primary | DS 4108 E p. 5 |
TB 69
Active chilled beams produce a two-dimensional flow and fall under a maximum of −8 K (p. 5). For the maximum cooling load, fig. 8 applies instead of fig. 7 (p. 6).
BF-V reach
Approx. 6 m deep and approx. 4 m wide (DS 4101 E p. 4).
DK-LIG/Z in the occupied zone
At 40 m³/(h·m) primary air, 0.14–0.18 m/s at most, with a gradient of 1 K/m up to 3.5 m ceiling height (DS 4108 E p. 4).
Typical mistakes
Where it goes wrong.
- The wrong type for the height. The IN-V2 is made for 2.7 to 5 m. Higher up, the IN-N6 (4–7 m) belongs there.
- Heating without low-level extract. When heating with the IN-N6, about half the return air should be extracted in the floor zone (DS 1125 E p. 6). Otherwise the warm air stays up.
- Treating a chilled beam like a ceiling diffuser. An active chilled beam discharges two-dimensionally and is limited to −8 K (TB 69 p. 5).
- A passive chilled beam above a fixed workstation. The DK-F has no primary air: cooled air falls straight down. The datasheet rules out fixed workstations beneath it (DS 4091 E p. 2).
The types in the collection
Linear diffusers: IN-V · IN-N6 · IN-V XTRA
Wall: BF-V
Chilled beams: DK-LIG/Z · DK-LIG/E · DK-LIG-EW · DK-LIO-TV
Façade and floor: IG-M-LB · IG-M-SB · IG-Q-SB (induction with displacement)
Chilled sail with induction: AVACS
Where you’ll find it
Krantz induction diffusers in Dutch projects, according to the old Peek website: De Nobel, Leiden (IN-V2); Shell, Rijswijk (IN-V); SNS Reaal, Utrecht (IN-V2); Slotervaart Hospital, Amsterdam (IN-V2 in a plastered ceiling).
Your host
Tell Pia about your space.
Pia is Peek's digital host. Describe your hall or building, and she will show you the Krantz components that fit.
I'm Pia. Shall I show you around?
Pia is an AI avatar, not a person.
with sound and microphone
Your voice and the conversation go via Runway in the United States, where privacy protection is weaker than in the EU; we do not yet have a data processing agreement with them. By clicking the start button you give your explicit consent to this (see the privacy statement).
Not live. Pia only starts when you click.
Click the start button in Pia's window. Your browser will then ask for your microphone.
Prefer a call? Leave your name and number and we'll call you back. Or chat with Pia using the button at the bottom right.
Or call us: +31 (0)73 820 02 88