Krantz Components

Induction · Mixingseen from below

DK-LIG/Z

Active chilled beam, two-way discharge

blue = cool supply air orange = warm air

Move through the air · click or hold for a swirl burstTap or hold for a swirl burst

Primary air from nozzles draws room air through the heat exchanger and blows the mixture horizontally along the ceiling to both sides.

DK-LIG/Z Active chilled beam, two-way discharge by Krantz
DK-LIG/ZInduction · induction
Cooling capacity
total 363–826 W/m (435–2477 W per unit) at water – room ΔT −10 K and air −8 Kp. 5
Heating capacity
171–352 W/m at water ΔT 15 K, isothermal primary airp. 5
Primary air volume
15–90 m³/(h·m); mondstukken 3–8 mmp. 5
Source · DS 4108 EKrantz, Active chilled beam DK-LIG/Z, DS 4108 E 05.2012

Stylised view, not a measurement

How the DK-LIG/Z works.

Primary air from nozzles draws room air through the heat exchanger and blows the mixture horizontally along the ceiling to both sides.

Applications: offices; low storey heights in new build and refurbishment (p. 6).

Krantz, Active chilled beam DK-LIG/Z, DS 4108 E 05.2012.

Technical data DK-LIG/Z

Krantz, Active chilled beam DK-LIG/Z, DS 4108 E 05.2012.

Page numbers are PDF pages of the data sheet.

Download documents

Request CAD/BIM

We will send you the available CAD or BIM files for the DK-LIG/Z, or call you to hear exactly what you need.

We use your details only to handle this request and do not store them on the website. More in our privacy statement.

Air

Specifications of the DK-LIG/Z with the source of each value · Air
PropertyValue · Source
Cooling capacity total 363–826 W/m (435–2477 W per unit) at water – room ΔT −10 K and air −8 K p. 5
Heating capacity 171–352 W/m at water ΔT 15 K, isothermal primary air p. 5
Primary air volume 15–90 m³/(h·m); mondstukken 3–8 mm p. 5
Air velocities bij 40 m³/(h·m) max. 0.14–0.18 m/s in verblijfszone (ca. 400 W/m); verticale gradiënt 1 K/m bij plafondhoogte ≤ 3.5 m p. 4
Sound LWA field in the specification text; no table found in the text p. 8

Design

Specifications of the DK-LIG/Z with the source of each value · Design
PropertyValue · Source
Sizes length 1200–3000 mm (steps of 300 mm); width 597 mm; height 300 mm p. 7
Weight 28–65 kg (1200–3000 mm) p. 3
Connections water: calibrated pipe ends Ø 15 mm (push-in or press); air: spigot DN 100/125 (end face also 150) p. 3
Options and versions 2- or 4-pipe system; spigot left, right or at the end face; various screen perforations p. 2

Your host

Tell Pia about your space.

Pia is Peek's digital host. Describe your hall or building, and she will show you the Krantz components that fit.

I'm Pia. Shall I show you around?

Pia is an AI avatar, not a person.

with sound and microphone

Your voice and the conversation go via Runway in the United States, where privacy protection is weaker than in the EU; we do not yet have a data processing agreement with them. By clicking the start button you give your explicit consent to this (see the privacy statement).

Not live. Pia only starts when you click.

Prefer a call? Leave your name and number and we'll call you back. Or chat with Pia using the button at the bottom right.

Or call us: +31 (0)73 820 02 88

Video call with Pia

What do you think of the new site?

Your answer helps us improve the site.

Your rating

1 = needs a lot of work, 5 = very good

We receive your rating, your text, the page you were on and, only if you fill it in, your email address, by email at Peek. More in the privacy statement.