Krantz Components

Jet · Inductionin section

BF-V

Broad multiplex outlet

blue = cool supply air orange = warm air

Move through the air · click or hold for a swirl burstTap or hold for a swirl burst

Rotating nozzle discs, each with seven thin jets, entrain the soft air from the perforated face plate. The result is a broad, stable fan of air that can also be aimed asymmetrically.

BF-V Broad multiplex outlet by Krantz
BF-VJet · wall
Max. ΔT cooling
−10 Kp. 4
Max. ΔT heating
+10 Kp. 4
Source · DS 4101 EKrantz, Broad multiplex outlet BF-V, DS 4101 E 04.2016/1

Stylised view, not a measurement

How the BF-V works.

Rotating nozzle discs, each with seven thin jets, entrain the soft air from the perforated face plate. The result is a broad, stable fan of air that can also be aimed asymmetrically.

Applications: restaurants, meeting rooms, schools, offices, hotel rooms; replacing existing wall grilles; on fan coils (p. 2). Krantz references in the Netherlands: Chassé Theater, Breda; Zuidplein police station, Rotterdam; Museum aan het Vrijthof, Maastricht (old Peek site)

Krantz, Broad multiplex outlet BF-V, DS 4101 E 04.2016/1.

Technical data BF-V

Discharge height
montagehoogte 2.2–4.0 mp. 7
Max. ΔT cooling
−10 Kp. 4
Volume flow
1-row 80–270 m³/hp. 3

Krantz, Broad multiplex outlet BF-V, DS 4101 E 04.2016/1.

Page numbers are PDF pages of the data sheet.

Download documents

Request IFC/STEP

DXF and RFA for the BF-V are on MagiCAD Cloud. We will request IFC or STEP from Krantz for you, or call you to hear exactly what you need.

We use your details only to handle this request and do not store them on the website. More in our privacy statement.

Air

Specifications of the BF-V with the source of each value · Air
PropertyValue · Source
Volume flow 1-row 80–270 m³/h; 2-row 160–540 m³/h (two ranges V1/V2 per length) p. 3
Max. ΔT cooling −10 K p. 4
Max. ΔT heating +10 K p. 4
Discharge height montagehoogte 2.2–4.0 m; min. 50 mm onder plafond p. 7
Penetration depth / throw reach length approx. 6 m, reach width approx. 4 m p. 4
Example sound and pressure drop classroom example 2-row 1,000 V2 FC, 470 m³/h: approx. 33 dB(A), approx. 11 Pa p. 4

Design

Specifications of the BF-V with the source of each value · Design
PropertyValue · Source
Sizes nominale lengte 600/800/1 000 mm (LA 580/760/940 mm); inbouwhoogte 146 mm (1-rij) / 238 mm (2-rij); 2.3–7.2 kg; 6–20 sproeischijven p. 3
Materials and finish face plate galvanised steel RAL 9010; nozzle discs polycarbonate white or black on black ABS carrier; optional perforated design plate RAL 9010 p. 8
Connections FC = open achterzijde voor fancoil; FL = 1 of 2 tuiten (DN 125–DN 200) met klep voor flexibele slang p. 2
Options and versions 1- or 2-row; perforated design plate (PF); position left/centre/right; extract version BF-V-AB (DS 4101 supplement 07.2020, FL only, 160–300 m³/h 1-row, 300–700 m³/h 2-row); mounting frame for duct installation p. 8

Your host

Tell Pia about your space.

Pia is Peek's digital host. Describe your hall or building, and she will show you the Krantz components that fit.

I'm Pia. Shall I show you around?

Pia is an AI avatar, not a person.

with sound and microphone

Your voice and the conversation go via Runway in the United States, where privacy protection is weaker than in the EU; we do not yet have a data processing agreement with them. By clicking the start button you give your explicit consent to this (see the privacy statement).

Not live. Pia only starts when you click.

Prefer a call? Leave your name and number and we'll call you back. Or chat with Pia using the button at the bottom right.

Or call us: +31 (0)73 820 02 88

Video call with Pia

What do you think of the new site?

Your answer helps us improve the site.

Your rating

1 = needs a lot of work, 5 = very good

We receive your rating, your text, the page you were on and, only if you fill it in, your email address, by email at Peek. More in the privacy statement.