How the DW-V2-DR works.
The DW-V2 with a hidden twist element at the inlet. The jet rotates and the throw is roughly halved, for rooms where a plain nozzle would reach too far.
Applications: long narrow rooms; combined with jet nozzles for high flows or a uniform appearance (p. 2).
Krantz, Twist nozzle DW-V2-…-DR, DS 1235e 10.2025.
Smoke test
Airflow in the Krantz lab.
A real smoke test in the Krantz flow laboratory: this is how air leaves the DW-V2-DR.
Technical data DW-V2-DR
- Discharge height
- min. montagehoogte 2.8 mp. 3
- Max. ΔT cooling
- −8 Kp. 3
- Volume flow
- 35–1,850 m³/hp. 2
Krantz, Twist nozzle DW-V2-…-DR, DS 1235e 10.2025.
Page numbers are PDF pages of the data sheet.
Download documents
Air
| Property | Value · Source |
|---|---|
| Volume flow | 35–1,850 m³/h for DN 80–DN 300 (table 1) p. 2 |
| Max. ΔT cooling | −8 K p. 3 |
| Max. ΔT heating | +6 K p. 3 |
| Discharge height | min. montagehoogte 2.8 m (DN 80) tot 4.5 m (DN 300) p. 3 |
| Penetration depth / throw | up to approx. 17 m p. 3 |
| Example sound and pressure drop | rekenvoorbeeld: DN 200, 560 m³/h, worp 8 m: 34 dB(A), 29 Pa, 4.9 m/s p. 14 |
Design
| Property | Value · Source |
|---|---|
| Sizes | as DW-V2, DN 80–DN 300 p. 7 |
| Materials and finish | as DW-V2; twist element black-painted galvanised steel p. 17 |
| Connections | K, R, F, B (as DW-V2) p. 4 |
| Options and versions | manually, electrically or thermostatically adjustable as DW-V2 p. 16 |
Your host
Tell Pia about your space.
Pia is Peek's digital host. Describe your hall or building, and she will show you the Krantz components that fit.
I'm Pia. Shall I show you around?
Pia is an AI avatar, not a person.
with sound and microphone
Not live. Pia only starts when you click.
Click the start button in Pia's window. Your browser will then ask for your microphone.
Prefer a call? Leave your name and number and we'll call you back. Or chat with Pia using the button at the bottom right.
Or call us: +31 (0)73 820 02 88