Krantz Components

Space · high containment

Air that must stay inside.

In a laboratory with a high biosafety level, in pharmaceutical production or in a nuclear installation, air is no longer a comfort question. It has to be filtered, flow in a controlled way and must not escape anywhere. For this, Peek supplies the filter and shut-off systems of Krantz Filter- und Absperrsysteme in the Netherlands.

The challenge

  • Pressure differences between rooms that hold even in a fault.
  • Filter change without exposing the technician or the surroundings.
  • Gas-tight isolation of ducts, verifiable after installation.
  • In nuclear technology: blast pressure waves and seismic requirements.

The approach

In the duct: filtration

SCF hightec Triple S

Stainless steel filter housing with triple sealing system, bag-in/bag-out, in-situ scanner to EN ISO 29463-4 and decontamination connections; for high-security laboratories of level 3 and 4; max. 3,400 m³/h nominal (krantz.de; old Peek website).

SCF hightec

Modular safe-change filter housing up to 48,000 m³/h; housing and filter seat tight to DIN 25 496 (krantz.de).

SCF classic, GS, MFU, RHF

Compact stainless steel filter housing, housing for circular ducts, mobile unit and re-cleanable system (krantz.de).

Filter elements

HEPA H13 and H14 to DIN EN 1822, sorption element WFZ, carbon cartridges (krantz.de; old Peek website).

In the duct: isolating and holding pressure

Gas-tight shut-off dampers: GD-C (circular, DN 80–400, 10,000 Pa), GD-R (rectangular, fail-safe possible) and GD-S (inflatable seal), gas-tight to DIN 25 496 (krantz.de; old Peek website).

Non-return damper: RK-E20, blast damper RK-F10 (0.45 bar, without auxiliary power), pressure relief dampers KL-E, KL-EM, KL-ETE and KL-ETM for duct protection and pressure cascades of 50–150 Pa between rooms (krantz.de; old Peek website).

Around the installation

Gas-tight doors: GT in stainless steel, bag sealing unit HSD for contamination-free filter change, leak tester LTD for test grooves of dampers and filter seats (krantz.de).

The types

Filtration (Krantz Filter- und Absperrsysteme): SCF hightec Triple S · SCF hightec · SCF classic · GS · MFU · RHF · HEPA H13 / H14 · WFZ · CFH · Carbon cartridges

Dampers and other (Krantz Filter- und Absperrsysteme): GD-C · GD-R · GD-S · ND-J · RK-E20 · RK-F10 · KL · GT · HSD · LTD

References

ProjectCitySupplied according to the source
BSL-3 TB lab, GGDAmsterdamHEPA filter system SCF hightec
Laboratory building O2AmsterdamSCF hightec · gas-tight dampers GD-C · non-return dampers RK-E20
RIVMBilthovennot stated
ECN/NRGPettennot stated

More laboratories →

Your host

Tell Pia about your space.

Pia is Peek's digital host. Describe your hall or building, and she will show you the Krantz components that fit.

I'm Pia. Shall I show you around?

Pia is an AI avatar, not a person.

with sound and microphone

Your voice and the conversation go via Runway in the United States, where privacy protection is weaker than in the EU; we do not yet have a data processing agreement with them. By clicking the start button you give your explicit consent to this (see the privacy statement).

Not live. Pia only starts when you click.

Prefer a call? Leave your name and number and we'll call you back. Or chat with Pia using the button at the bottom right.

Or call us: +31 (0)73 820 02 88

Video call with Pia

What do you think of the new site?

Your answer helps us improve the site.

Your rating

1 = needs a lot of work, 5 = very good

We receive your rating, your text, the page you were on and, only if you fill it in, your email address, by email at Peek. More in the privacy statement.