Krantz Components

Stralingskoeling convectiein the studio

SKS Slimline

Static chilled ceiling with low installation height

SKS SLIMLINE Static chilled ceiling with low installation height by Krantz
Image: Krantz Components

High-capacity elements for exposed or concealed installation that cool and heat silently at a low installation height.

SKS SlimlineStralingskoeling convectie · chilled ceiling
Overall height
200 mm; installation height ≥ 250 mmp. 3
System type
static cooling ceiling with vertical aluminium fins and optional PET sound-absorbing bafflesp. 2
Heating capacity
up to 210 W/m² (pipe spacing 100 mm) and 146 W/m² (150 mm) at ΔT 15 K (DIN EN 14037)p. 7
Source · DS 4206 EKrantz, Static cooling ceiling system SKS Slimline, DS 4206 E 05.2026

How the SKS Slimline works.

High-capacity elements for exposed or concealed installation that cool and heat silently at a low installation height.

Applications: from the comfort sector to industry; hygienic applications; combinable with linear outlets such as the IN-V2 (DS 4206 E p. 2).

Krantz, Static cooling ceiling system SKS Slimline, DS 4206 E 05.2026.

Technical data SKS Slimline

Krantz, Static cooling ceiling system SKS Slimline, DS 4206 E 05.2026.

Page numbers are PDF pages of the data sheet.

Download documents

Request CAD/BIM

We will send you the available CAD or BIM files for the SKS Slimline, or call you to hear exactly what you need.

We use your details only to handle this request and do not store them on the website. More in our privacy statement.

Air

Specifications of the SKS Slimline with the source of each value · Air
PropertyValue · Source
Cooling capacity up to 224 W/m² of cooling element at ΔT −10 K (pipe spacing 100 mm) and up to 155 W/m² (150 mm, standard), DIN EN 14240, freely suspended p. 7
Heating capacity up to 210 W/m² (pipe spacing 100 mm) and 146 W/m² (150 mm) at ΔT 15 K (DIN EN 14037) p. 7

Design

Specifications of the SKS Slimline with the source of each value · Design
PropertyValue · Source
Overall height 200 mm; installation height ≥ 250 mm p. 3
System type static cooling ceiling with vertical aluminium fins and optional PET sound-absorbing baffles p. 2
Sizes length 1,000 – 4,000 mm (increments of 10 mm); width 236 – 1,036 mm (pipe spacing 100 mm) or 336 – 1,086 mm (150 mm); max. 3 m² per element p. 3
Materials and finish aluminium lamellen; koperbuis ø 12 x 0.4 mm; verzinkt stalen traverse; optioneel poedercoating; baffles van PET p. 3
Operating pressure and weight 6 bar (push-fit), up to 15 bar with screw or press connection; approx. 19 kg/m² (100 mm) or 16 kg/m² (150 mm) filled p. 3

Your host

Tell Pia about your space.

Pia is Peek's digital host. Describe your hall or building, and she will show you the Krantz components that fit.

I'm Pia. Shall I show you around?

Pia is an AI avatar, not a person.

with sound and microphone

Your voice and the conversation go via Runway in the United States, where privacy protection is weaker than in the EU; we do not yet have a data processing agreement with them. By clicking the start button you give your explicit consent to this (see the privacy statement).

Not live. Pia only starts when you click.

Prefer a call? Leave your name and number and we'll call you back. Or chat with Pia using the button at the bottom right.