Krantz Components

Convection · Radiant coolingin section

SKS-4/3-duo

Static chilled ceiling for high cooling loads

blue = cool supply air orange = warm air

Move through the air · click for a puff of airTap for a puff of air

A version of the SKS-4/3 with a different fin arrangement, for very high cooling capacities above an open ceiling.

SKS-4/3-DUO Static chilled ceiling for high cooling loads by Krantz
SKS-4/3-duoConvection · chilled ceiling
Cooling capacity
216 W/m² cooling element without modular ceiling (with reference to DIN 4715)p. 2
Overall height
120 mm; mounting height 200 mmp. 2
System type
static cooling ceiling with increased capacity, for open modular ceilingsp. 2
Source · DS 4143 EKrantz, Static cooling ceiling system SKS-4/3-duo, DS 4143 E 03.2008

Stylised view, not a measurement

How the SKS-4/3-duo works.

A version of the SKS-4/3 with a different fin arrangement, for very high cooling capacities above an open ceiling.

Applications: offices with high heat loads, TV studios, technical and industrial rooms (p. 2).

Krantz, Static cooling ceiling system SKS-4/3-duo, DS 4143 E 03.2008.

Technical data SKS-4/3-duo

Installation height
mounting height 200 mmp. 2

Krantz, Static cooling ceiling system SKS-4/3-duo, DS 4143 E 03.2008.

Page numbers are PDF pages of the data sheet.

Download documents

Request IFC/STEP

DXF and RFA for the SKS-4/3-duo are on MagiCAD Cloud. We will request IFC or STEP from Krantz for you, or call you to hear exactly what you need.

We use your details only to handle this request and do not store them on the website. More in our privacy statement.

Air

Specifications of the SKS-4/3-duo with the source of each value · Air
PropertyValue · Source
Cooling capacity 216 W/m² cooling element without modular ceiling (with reference to DIN 4715) p. 2
Cooling capacity (Peek info, id 290) approx. 215 W/m² at mean water temperature 16 °C and room 26 °C p. 4
Heating capacity (Peek info, id 290) approx. 125 W/m² of element at 20 °C room and mean water 38 °C; recommended max. 35 W/m² of floor for comfort reasons; heating approx. 60% radiation / 40% convection p. 2
Heating capacity (Krantz e-mail, id 289) approx. 350 W/m² of element achievable at flow 48 °C / return 43 °C and room 20 °C (freely suspended or f.Q. 90%, coverage approx. 30%); spread max. 5 K; max. 100 W/m² of floor in the occupied zone with turbulent ceiling ventilation p. 1

Design

Specifications of the SKS-4/3-duo with the source of each value · Design
PropertyValue · Source
Sizes nominal length 1000–4000 mm in steps of 100 mm; width 400–1200 mm in steps of 100 mm; height H 120 mm; pipe spacing T 100 mm p. 2
Installation height mounting height 200 mm p. 2
Materials and finish copper meander Ø 12 mm, aluminium fins, U-shaped sheet steel frame; powder coating RAL (standard RAL 9005) p. 2
Connections buiseinden voor insteek- of persverbinding; 2 aansluitingen bij ca. ≤ 2.5 m², anders 4 p. 2
Operating pressure and weight 6 bar; approx. 13 kg/m² filled p. 2
Ceiling type open modular ceilings; correction factors for free area (20–75%) and coverage (30–80%) in Graph B p. 2
Overall height 120 mm; mounting height 200 mm p. 2
System type static cooling ceiling with increased capacity, for open modular ceilings p. 2

Your host

Tell Pia about your space.

Pia is Peek's digital host. Describe your hall or building, and she will show you the Krantz components that fit.

I'm Pia. Shall I show you around?

Pia is an AI avatar, not a person.

with sound and microphone

Your voice and the conversation go via Runway in the United States, where privacy protection is weaker than in the EU; we do not yet have a data processing agreement with them. By clicking the start button you give your explicit consent to this (see the privacy statement).

Not live. Pia only starts when you click.

Prefer a call? Leave your name and number and we'll call you back. Or chat with Pia using the button at the bottom right.