Space · high containment
Air that must stay inside.
In a laboratory with a high biosafety level, in pharmaceutical production or in a nuclear installation, air is no longer a comfort question. It has to be filtered, flow in a controlled way and must not escape anywhere. For this, Peek supplies the filter and shut-off systems of Krantz Filter- und Absperrsysteme in the Netherlands.
The challenge
- Pressure differences between rooms that hold even in a fault.
- Filter change without exposing the technician or the surroundings.
- Gas-tight isolation of ducts, verifiable after installation.
- In nuclear technology: blast pressure waves and seismic requirements.
The approach
In the duct: filtration
SCF hightec Triple S
Stainless steel filter housing with triple sealing system, bag-in/bag-out, in-situ scanner to EN ISO 29463-4 and decontamination connections; for high-security laboratories of level 3 and 4; max. 3,400 m³/h nominal (krantz.de; old Peek website).
SCF hightec
Modular safe-change filter housing up to 48,000 m³/h; housing and filter seat tight to DIN 25 496 (krantz.de).
SCF classic, GS, MFU, RHF
Compact stainless steel filter housing, housing for circular ducts, mobile unit and re-cleanable system (krantz.de).
Filter elements
HEPA H13 and H14 to DIN EN 1822, sorption element WFZ, carbon cartridges (krantz.de; old Peek website).
In the duct: isolating and holding pressure
Gas-tight shut-off dampers: GD-C (circular, DN 80–400, 10,000 Pa), GD-R (rectangular, fail-safe possible) and GD-S (inflatable seal), gas-tight to DIN 25 496 (krantz.de; old Peek website).
Non-return damper: RK-E20, blast damper RK-F10 (0.45 bar, without auxiliary power), pressure relief dampers KL-E, KL-EM, KL-ETE and KL-ETM for duct protection and pressure cascades of 50–150 Pa between rooms (krantz.de; old Peek website).
Around the installation
Gas-tight doors: GT in stainless steel, bag sealing unit HSD for contamination-free filter change, leak tester LTD for test grooves of dampers and filter seats (krantz.de).
The types
Filtration (Krantz Filter- und Absperrsysteme): SCF hightec Triple S · SCF hightec · SCF classic · GS · MFU · RHF · HEPA H13 / H14 · WFZ · CFH · Carbon cartridges
Dampers and other (Krantz Filter- und Absperrsysteme): GD-C · GD-R · GD-S · ND-J · RK-E20 · RK-F10 · KL · GT · HSD · LTD
References
| Project | City | Supplied according to the source |
|---|---|---|
| BSL-3 TB lab, GGD | Amsterdam | HEPA filter system SCF hightec |
| Laboratory building O2 | Amsterdam | SCF hightec · gas-tight dampers GD-C · non-return dampers RK-E20 |
| RIVM | Bilthoven | not stated |
| ECN/NRG | Petten | not stated |
Your host
Tell Pia about your space.
Pia is Peek's digital host. Describe your hall or building, and she will show you the Krantz components that fit.
I'm Pia. Shall I show you around?
Pia is an AI avatar, not a person.
with sound and microphone
Not live. Pia only starts when you click.
Click the start button in Pia's window. Your browser will then ask for your microphone.
Prefer a call? Leave your name and number and we'll call you back. Or chat with Pia using the button at the bottom right.
Or call us: +31 (0)73 820 02 88