Air principle
From outlet to occupied zone.
At the outlet
Many radial slots, each with its own twisted, highly inductive jet. (DS 1146 E p. 5)
In the room
Mixing makes the velocity drop quickly. The flow rises with the thermal plumes, and warm air leaves the room at the ceiling. (DS 1146 E p. 5)
Construction
A swirl element with radial slots, a distribution basket (optionally with throttle damper) and a clamping ring with fixing, or a stepped bore in the floor panel. Optional plenum box. (DS 1146 E p. 2–3)
Technical data DB-E
- Max. ΔT
- ±10 K supply – returnp. 5
- Volume flow DN 150
- 20 – 50 m³/hp. 5
Krantz Components, Floor twist outlets DB-E, DS 1146 E 05.2015/1.
Page numbers are PDF pages of the data sheet.
Download documents
Air
| Property | Value · Source |
|---|---|
| Air distribution | twisted, highly inductive jets, upward DS 1146 E p. 5 |
| Volume flow DN 150 | 20 – 50 m³/h; in occupied areas max. 45 m³/h p. 5 |
| Volume flow DN 200 | 50 – 180 m³/h; in occupied areas max. 150 m³/h p. 5 |
| Max. ΔT | ±10 K supply – return p. 5 |
| Supply temperature | 18 – 30 °C p. 5 |
| Example | DN 200 with basket VSD, 150 m³/h: 38 Pa, 39 dB(A) p. 10 |
| Throw | not given as a figure; velocity profiles in the data sheet p. 7 – 8 |
Design
| Property | Value · Source |
|---|---|
| Sizes | DN 150 · DN 200; collar Ø 172 · 230 mm; plenum box 280 × 250 · 380 × 350 mm p. 3 |
| Material | swirl element polycarbonate RAL 7037, or aluminium (DN 200); basket polycarbonate black or steel; box galvanised steel p. 12 |
| Load rating | 7.5 kN (DN 150, PC) · 5.6 kN (DN 200, PC) · 12 kN (DN 200, Al); class "heavy" to EN 13264 p. 5 |
| Connection | directly from the floor plenum, or via plenum box with flexible duct p. 2 |
| Options | baskets VS/VSD, VK, VN/VND, VPD, VL; clamping ring, claw fixing or clamping nut; locking (DN 200) p. 11 |
Versions and sizes
Two sizes, polycarbonate or aluminium.
- DN 150
- DN 200
DS 1146 E p. 3
Finish
polycarbonate dust grey RAL 7037; DN 200 also in aluminium (p. 12)
In the floor
in the raised floor, with clamping ring or in a stepped bore (p. 2–3)
Applications
Where it belongs.
Offices, EDP and control rooms, and meeting rooms; the DN 200 for large volume flows (DS 1146 E p. 10).
Krantz references in the Netherlands: Schouwburg Kunstmin, Dordrecht; AEGON, The Hague; WTC Schiphol; the DB-E product page also lists Chassé Theater, Breda and the Public Library Amsterdam
When not: If users should aim the jet themselves, look at the DB-D (rotary, DS 4074e p. 5). If the air should spread low across the floor instead of rising, the Q-B fits (displacement, DS 4062 E p. 4).
Related in the collection
Same family, a different character.
| Type | What it is | Essence | Source |
|---|---|---|---|
| DB-D | Rotary floor twist outlet | inclined jet (approx. 30°), aimed by the user | DS 4074e p. 5 |
| BA-V | Adjustable floor outlet | a setting disc switches between swirl and displacement | DS 4047 E p. 2 |
| Q-B | Floor displacement outlet | air low and radial across the floor; up to 100 m³/h | DS 4062 E p. 2, p. 4 |
Video call with Pia
Tell Pia about your space.
Pia is Peek's digital host. Describe your hall or building, and she will show you the Krantz components that fit.
I'm Pia. Shall I show you around?
Pia is an AI avatar, not a person.
with sound and microphone
Your voice and the conversation go via Runway in the United States, where privacy protection is weaker than in the EU; we do not yet have a data processing agreement with them. By clicking the start button you give your explicit consent to this (see the privacy statement).
Not live. Pia only starts when you click.
Click the start button in Pia's window. Your browser will then ask for your microphone.
Prefer a call? Leave your name and number and we'll call you back. Or chat with Pia using the button at the bottom right.
Or call us: +31 (0)73 820 02 88