Krantz Components

Radiant cooling · Convectionin section

SKS-4/3

Static chilled ceiling, concealed or exposed

blue = cool supply air orange = warm air

Move through the air · click for a puff of airTap for a puff of air

Open finned registers with a copper meander below the concrete soffit, cooling the room by radiation and convection, also when concealed above an open suspended ceiling.

SKS-4/3 Static chilled ceiling, concealed or exposed by Krantz
SKS-4/3Radiant cooling · chilled ceiling
Overall height
85 mm; installation height ≥ 185 mmp. 3
Installation height
≥ 185 mm (min. 50 mm clear above and below the element)p. 3
Source · DS 4094 EKrantz, Static cooling ceiling system SKS-4/3, DS 4094 E 05.2007

Stylised view, not a measurement

How the SKS-4/3 works.

Open finned registers with a copper meander below the concrete soffit, cooling the room by radiation and convection, also when concealed above an open suspended ceiling.

Applications: offices; high cooling loads such as TV studios, technical rooms and industry; refurbishment thanks to the low installation height (p. 2).

Krantz, Static cooling ceiling system SKS-4/3, DS 4094 E 05.2007.

Technical data SKS-4/3

Installation height
≥ 185 mmp. 3

Krantz, Static cooling ceiling system SKS-4/3, DS 4094 E 05.2007.

Page numbers are PDF pages of the data sheet.

Download documents

Request IFC/STEP

DXF and RFA for the SKS-4/3 are on MagiCAD Cloud. We will request IFC or STEP from Krantz for you, or call you to hear exactly what you need.

We use your details only to handle this request and do not store them on the website. More in our privacy statement.

Air

Specifications of the SKS-4/3 with the source of each value · Air
PropertyValue · Source
Cooling capacity standard 175 W/m² cooling element (projected area), freely suspended without modular ceiling, to DIN 4715 p. 3
Cooling capacity (table) at 26 °C room / 16 – 18 °C water (9 K): 111–157 W/m² of element and 39–94 W/m² of ceiling area respectively, depending on free area and coverage 30–60% (Table A/B) p. 8
Cooling capacity (table 7 K) 85–120 W/m² of element and 30–72 W/m² of ceiling area respectively (Table C/D) p. 9
Recommended limit specific cooling capacity < 160 W/m² of element recommended for air velocities to DIN 1946 – 2 p. 9
Heating also suitable for heating, worthwhile with exposed installation or a modular ceiling with free area > 70%; no figure given p. 3
Water temperatures typical: flow 16 °C, return 18 °C; flow > 16 °C and water ΔT > 2 K recommended; min. water flow 70 l/h per element p. 8
Water pressure drop Δp = 1.81·10⁻⁵ · N(L+0.1) · V̇²; richtwaarde ≤ 20–30 kPa per element; rekenvoorbeeld 10.5 kPa p. 7
Sound no noise generation ('no noise') cited as a comfort advantage p. 9

Design

Specifications of the SKS-4/3 with the source of each value · Design
PropertyValue · Source
Sizes nominal length 1000–4000 mm in steps of 100 mm; width 350–1475 mm in steps of 125 mm; height 85 mm; area per element max. 5 m² p. 3
Installation height ≥ 185 mm (min. 50 mm clear above and below the element) p. 3
Materials and finish koperen meander 12 x 0.5 mm (Cu-DHP), aluminium extrusie-lamellen, verzinkte Z-profielen; standaard zwart gepoedercoat/natlak (RAL 9005-achtig), andere RAL-kleuren mogelijk p. 3
Connections pipe ends Ø 12 mm for push-in, press or soldered connection; pipe spacing 125 mm p. 3
Operating pressure and weight 6 bar (max. 16 bar); approx. 7–9 kg/m² filled p. 3
Ceiling type open modular ceilings (metal: rectangular/square tile, panel, strip); acoustic mats on perforated tiles cannot be combined p. 9
Overall height 85 mm; installation height ≥ 185 mm p. 3
System type static cooling ceiling (radiation and convection), concealed or exposed, freely suspended or in an open modular ceiling p. 2

Your host

Tell Pia about your space.

Pia is Peek's digital host. Describe your hall or building, and she will show you the Krantz components that fit.

I'm Pia. Shall I show you around?

Pia is an AI avatar, not a person.

with sound and microphone

Your voice and the conversation go via Runway in the United States, where privacy protection is weaker than in the EU; we do not yet have a data processing agreement with them. By clicking the start button you give your explicit consent to this (see the privacy statement).

Not live. Pia only starts when you click.

Prefer a call? Leave your name and number and we'll call you back. Or chat with Pia using the button at the bottom right.