WSD

Wall slot diffuser

WSD Wall slot diffuser by Krantz

blue = cool supply air orange = warm air

Move through the air · click or hold for a swirl burstDrag the diffuser to rotate · tap beside it for a swirl burst

A slim slot outlet in the corridor wall. After 1 – 2 m the flow becomes diffuse and glides as a layer across the floor towards the façade.

WSD Wall slot diffuser by Krantz
WSDInduction · wall
Discharge height
aanbevolen 2.4–3.5 mp. 2
Max. ΔT heating
+6 Kp. 2
Source · DS 4119 EKrantz, Wall slot diffuser WSD, DS 4119 E 12.2013

Stylised view, not a measurement

How the WSD works.

A slim slot outlet in the corridor wall. After 1 – 2 m the flow becomes diffuse and glides as a layer across the floor towards the façade.

Applications: office and administration buildings, preferably with concrete core activation or chilled ceilings; at DR 20 % also shops, museums and restaurants (p. 2).

Krantz, Wall slot diffuser WSD, DS 4119 E 12.2013.

Smoke test

Airflow in the Krantz lab.

A real smoke test in the Krantz flow laboratory: this is how air leaves the WSD.

WSDVideo: Krantz Komponenten · Real smoke test in the laboratory

Technical data WSD

Discharge height
aanbevolen 2.4–3.5 mp. 2
Max. ΔT cooling
−8 Kp. 2
Volume flow
max. per metre: 1-row 120 m³/(h·m)p. 2

Krantz, Wall slot diffuser WSD, DS 4119 E 12.2013.

Page numbers are PDF pages of the data sheet.

Download documents

Request IFC/STEP

DXF and RFA for the WSD are on MagiCAD Cloud. We will request IFC or STEP from Krantz for you, or call you to hear exactly what you need.

We use your details only to handle this request and do not store them on the website. More in our privacy statement.

Air

Specifications of the WSD with the source of each value · Air
PropertyValue · Source
Volume flow max. per metre: 1-row 120 m³/(h·m) at DR 15% and 39 [140] at DR 20%; 2-row 53 [190] and 240 m³/(h·m) respectively p. 2
Max. ΔT cooling −8 K (DR 15%) to −10 K (DR 20%) p. 2
Max. ΔT heating +6 K p. 2
Discharge height aanbevolen 2.4–3.5 m p. 2
Penetration depth / throw suitable for room depths > 4 m p. 2
Example sound and pressure drop restaurant example 2-row 1,050 mm: approx. 43 dB(A), 36 Pa; office example combined: 30 dB(A), supply 33 Pa / return 40 Pa p. 5

Design

Specifications of the WSD with the source of each value · Design
PropertyValue · Source
Sizes lengte 525 / 1 050 / 1 125 mm; voor wanddikte 100 mm; 2.6–8.9 kg p. 3
Materials and finish slot profile aluminium, powder-coated RAL 9010 or natural anodised; distribution elements polycarbonate black or white; plenum box galvanised steel p. 11
Connections ronde tuit achter; type Z in de wand, type H achter de wand; optionele klep bedienbaar vanuit ruimte p. 3
Options and versions supply, extract or combined; 1- or 2-row (3-row on request); acoustic lining class A2 (often no crosstalk attenuator required) p. 10

Your host

Tell Pia about your space.

Pia is Peek's digital host. Describe your hall or building, and she will show you the Krantz components that fit.

I'm Pia. Shall I show you around?

Pia is an AI avatar, not a person.

with sound and microphone

Your voice and the conversation go via Runway in the United States, where privacy protection is weaker than in the EU; we do not yet have a data processing agreement with them. By clicking the start button you give your explicit consent to this (see the privacy statement).

Not live. Pia only starts when you click.

Prefer a call? Leave your name and number and we'll call you back. Or chat with Pia using the button at the bottom right.

Or call us: +31 (0)73 820 02 88

Video call with Pia

What do you think of the new site?

Your answer helps us improve the site.

Your rating

1 = needs a lot of work, 5 = very good

We receive your rating, your text, the page you were on and, only if you fill it in, your email address, by email at Peek. More in the privacy statement.