Krantz Components

Displacement · Swirlin section

VA-RV / VA-RN

Rectangular displacement outlet

blue = cool supply air orange = warm air

Move through the air · click for a gentle displacement flowTap for a gentle displacement flow

A wide, shallow box on the floor along the wall. Cool air glides low up to 20 m into the hall; in the adjustable VA-RV a damper turns warm air towards the floor.

VA-RV / VA-RN Rectangular displacement outlet by Krantz
VA-RV / VA-RNDisplacement · displacement
Max. ΔT cooling
max. −8 K supply – roomp. 5
Source · DS 4009 EKrantz, Rectangular displacement outlet VA-RN / with adjustment device VA-RV, DS 4009 E 06.2012

Stylised view, not a measurement

How the VA-RV / VA-RN works.

A wide, shallow box on the floor along the wall. Cool air glides low up to 20 m into the hall; in the adjustable VA-RV a damper turns warm air towards the floor.

Applications: printing works, ironing and laundry plants, foundries and textile cleaning (p. 4).

Krantz, Rectangular displacement outlet VA-RN / with adjustment device VA-RV, DS 4009 E 06.2012.

Smoke test

Airflow in the Krantz lab.

A real smoke test in the Krantz flow laboratory: this is how air leaves the VA-RV / VA-RN.

VA-RV / VA-RN, coolingVideo: Krantz Komponenten · Real smoke test in the laboratory

Technical data VA-RV / VA-RN

Max. ΔT cooling
max. −8 K supply – roomp. 5
Volume flow
up to 2,500 m³/(h·m)p. 5

Krantz, Rectangular displacement outlet VA-RN / with adjustment device VA-RV, DS 4009 E 06.2012.

Page numbers are PDF pages of the data sheet.

Download documents

Request CAD/BIM

We will send you the available CAD or BIM files for the VA-RV / VA-RN, or call you to hear exactly what you need.

We use your details only to handle this request and do not store them on the website. More in our privacy statement.

Air

Specifications of the VA-RV / VA-RN with the source of each value · Air
PropertyValue · Source
Volume flow up to 2,500 m³/(h·m); diagram approx. 505 – 2,520 m³/(h·m), depending on distance to workplace p. 5
Max. ΔT cooling max. −8 K supply – room p. 5
Max. ΔT heating max. +6 K (adjustable VA-RV only) p. 5
Penetration depth / throw cooling up to 20 m; heating (VA-RV) 10 – 15 m p. 2
Example sound and pressure drop example size 2, B 2 m, 1,980 m³/(h·m): 54 dB(A), 37 Pa p. 4
Load factors pollutant load factor 20 % and heat load factor 45 % (mixing ventilation 90 – 100 %); only 45 % of the volume flow required p. 2

Design

Specifications of the VA-RV / VA-RN with the source of each value · Design
PropertyValue · Source
Sizes height 765 (size 1) or 1,150 mm (size 2); width 1,000 / 1,500 / 2,000 / 2,500 mm; depth 350 mm; weight 38 – 112 kg p. 2
Materials and finish galvanised sheet steel, visible parts optionally powder-coated RAL; swirl elements of polycarbonate, mass-coloured approx. RAL 7037 dusty grey p. 5
Connections spigot on top (centre, left or right) with flange for standard angle flanges p. 2
Options and versions VA-RN not adjustable; VA-RV with damper, manual (lever) or Belimo NM24A-SR / Siemens GLB161.1E 0 – 10 V; special lengths on request p. 5

Your host

Tell Pia about your space.

Pia is Peek's digital host. Describe your hall or building, and she will show you the Krantz components that fit.

I'm Pia. Shall I show you around?

Pia is an AI avatar, not a person.

with sound and microphone

Your voice and the conversation go via Runway in the United States, where privacy protection is weaker than in the EU; we do not yet have a data processing agreement with them. By clicking the start button you give your explicit consent to this (see the privacy statement).

Not live. Pia only starts when you click.

Prefer a call? Leave your name and number and we'll call you back. Or chat with Pia using the button at the bottom right.

Or call us: +31 (0)73 820 02 88

Video call with Pia

What do you think of the new site?

Your answer helps us improve the site.

Your rating

1 = needs a lot of work, 5 = very good

We receive your rating, your text, the page you were on and, only if you fill it in, your email address, by email at Peek. More in the privacy statement.